2.4 Synchronism and voltage check (optional)
No.
Information
2908
>Usy1>Usy2<
2909
>Usy1<Usy2>
2910
>Usy1<Usy2<
2911
>Sync. o/ride
2930
Sync. on/off BI
2931
Sync. OFF
2932
Sync. BLOCK
2934
Sync. faulty
2935
Sync.Tsup.Exp
2936
Sync. req.CNTRL
2941
Sync. running
2942
Sync.Override
2943
Synchronism
2944
SYNC Usy1>Usy2<
2945
SYNC Usy1<Usy2>
2946
SYNC Usy1<Usy2<
2947
Sync. Udiff>
2948
Sync. fdiff>
2949
Sync. φ-diff>
2951
Sync. release
2961
Sync.CloseCmd
2970
SYNC fsy2>>
2971
SYNC fsy2<<
2972
SYNC fsy1>>
2973
SYNC fsy1<<
2974
SYNC Usy2>>
2975
SYNC Usy2<<
2976
SYNC Usy1>>
2977
SYNC Usy1<<
2978
SYNC Usy2>Usy1
2979
SYNC Usy2<Usy1
2980
SYNC fsy2>fsy1
2981
SYNC fsy2<fsy1
2982
SYNC φsy2>φsy1
2983
SYNC φsy2<φsy1
96
Type of
Comments
Informa-
tion
SP
>Sync-Prog. Usy1>Usy2<
SP
>Sync-Prog. Usy1<Usy2>
SP
>Sync-Prog. Usy1<Usy2<
SP
>Sync-Prog. Override ( bypass )
IntSP
Synchro-check ON/OFF via BI
OUT
Synchro-check is switched OFF
OUT
Synchro-check is BLOCKED
OUT
Synchro-check function faulty
OUT
Synchro-check supervision time expired
OUT
Synchro-check request by control
OUT
Synchronization is running
OUT
Synchro-check override/bypass
OUT
Synchronism detected
OUT
SYNC Condition Usy1>Usy2< true
OUT
SYNC Condition Usy1<Usy2> true
OUT
SYNC Condition Usy1<Usy2< true
OUT
Sync. Voltage diff. greater than limit
OUT
Sync. Freq. diff. greater than limit
OUT
Sync. Angle diff. greater than limit
OUT
Synchronism release (to ext. AR)
OUT
Close command from synchro-check
OUT
SYNC frequency fsy2 > (fn + 3Hz)
OUT
SYNC frequency fsy2 < (fn + 3Hz)
OUT
SYNC frequency fsy1 > (fn + 3Hz)
OUT
SYNC frequency fsy1 < (fn + 3Hz)
OUT
SYNC voltage Usy2 >Umax (P.3504)
OUT
SYNC voltage Usy2 < U> (P.3503)
OUT
SYNC voltage Usy1 >Umax (P.3504)
OUT
SYNC voltage Usy1 < U> (P.3503)
OUT
SYNC Udiff too large (Usy2>Usy1)
OUT
SYNC Udiff too large (Usy2<Usy1)
OUT
SYNC fdiff too large (fsy2>fsy1)
OUT
SYNC fdiff too large (fsy2<fsy1)
OUT
SYNC PHIdiff too large (PHIsy2>PHIsy1)
OUT
SYNC PHIdiff too large (PHIsy2<PHIsy1)