Characteristics - Siemens SIPROTEC 4 7VK61 Manual

Breaker management device
Table of Contents

Advertisement

Introduction

1.3 Characteristics

1.3
Characteristics
General Features
Powerful 32-bit microprocessor system
Complete digital processing of measured values and control, from the sampling and digitizing of the
measure quantities up to the closing and tripping commands to the circuit breakers
Complete galvanic separation and interference immunity of the internal processing circuits from the
measurement, control, and power supply circuits by analog input transducers, binary inputs and outputs
and the DC/DC or AC/DC converters
Simple device operation using the integrated operator panel or a connected personal computer with
operator guidance
Storage of fault indications and instantaneous values for fault recording
Automatic reclosure function (optional)
For reclosure after 1-pole, 3-pole or 1-pole and 3-pole tripping
Single or multiple reclosure (up to eight reclosure attempts)
With separate action time setting for the first 4 reclose attempts, optionally without action times
With separate dead times after 1-pole and 3-pole tripping, separate for the first four reclosure attempts
Controlled optionally by protection pickup with separate dead times after 1-pole , 2-pole or 3-pole pickup
Optionally with adaptive dead time, reduced dead time and dead line check
Synchronism and voltage check (optional)
Verification of the synchronous conditions before reclosing after three-pole tripping
Fast measurement of the voltage difference U
difference f
Alternatively, check of the de-energized state before reclosing
Closing at asynchronous system conditions with consideration of the CB closing time to achieve system
re-connection when voltages are in phase
Settable minimum and maximum voltage
Verification of the synchronous conditions or de-energized state before manual closing of the circuit
breaker is possible with separate setting thresholds and states
Phase angle compensation for voltage measurement behind a transformer
Measuring voltages optionally phase-phase or phase-earth
Time Overcurrent Protection (optional, available with breaker failure protection)
Two definite time stages (DT) and one inverse time stage (IDMT), each for phase currents and earth
current
For inverse-time overcurrent protection select from various characteristics based on several standards
Blocking capability e.g. for reverse interlocking with any stage
Instantaneous tripping by any stage when switching onto a fault
Additional stage, e.g. stub protection, for fast tripping of faults between the current transformer and line
isolator (when the isolator switching status feedback is available); particularly well suited to substations
with 1
1
/
circuit breaker arrangements.
2
22
diff
, the phase angle difference φ
diff
C53000-G1176-C159-5, Edition 05.2018
and the frequency
diff
SIPROTEC 4, 7VK61, Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents