φB must be at least 3° apart. Incorrect parameter settings cause the indication 132
output.
2.7.1.7

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
2901
MEASURE. SUPERV
2902A
BALANCE U-LIMIT
2903A
BAL. FACTOR U
2904A
BALANCE I LIMIT
2905A
BAL. FACTOR I
2906A
ΣI THRESHOLD
2907A
ΣI FACTOR
2908A
T BAL. U LIMIT
2909A
T BAL. I LIMIT
2910
FUSE FAIL MON.
2911A
FFM U>(min)
2912A
FFM I< (max)
2913A
FFM U<max (3ph)
2914A
FFM Idelta (3p)
2915
V-Supervision
2916A
T V-Supervision
2941
φA
2942
φB
2943
I1>
2944
U1>
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
C
Setting Options
ON
OFF
10 .. 100 V
0.58 .. 0.95
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
0.10 .. 0.95
1A
0.05 .. 2.00 A
5A
0.25 .. 10.00 A
0.00 .. 0.95
5 .. 100 sec
5 .. 100 sec
ON
OFF
10 .. 100 V
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
2 .. 100 V
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
w/ CURR.SUP
w/ I> & CBaux
OFF
0.00 .. 30.00 sec
0 .. 359 °
0 .. 359 °
1A
0.05 .. 2.00 A
5A
0.25 .. 10.00 A
2 .. 70 V
φ Set wrong to be
Default Setting
Comments
ON
Measurement Supervision
50 V
Voltage Threshold for
Balance Monitoring
0.75
Balance Factor for Voltage
Monitor
0.50 A
Current Balance Monitor
2.50 A
0.50
Balance Factor for Current
Monitor
0.10 A
Summated Current Moni-
toring Threshold
0.50 A
0.10
Summated Current Moni-
toring Factor
5 sec
T Balance Factor for
Voltage Monitor
5 sec
T Current Balance Monitor
ON
Fuse Failure Monitor
30 V
Minimum Voltage
Threshold U>
0.10 A
Maximum Current
Threshold I<
0.50 A
15 V
Maximum Voltage
Threshold U< (3phase)
0.10 A
Delta Current Threshold
(3phase)
0.50 A
w/ CURR.SUP
Voltage Failure Supervision
3.00 sec
Delay Voltage Failure
Supervision
200 °
Limit setting PhiA
340 °
Limit setting PhiB
0.05 A
Minimum value I1>
0.25 A
20 V
Minimum value U1>
Functions
2.7 Monitoring Functions