Siemens SIPROTEC 4 7VK61 Manual page 297

Breaker management device
Table of Contents

Advertisement

Addr. Parameter
201
CT Starpoint
203
Unom PRIMARY
204
Unom SECONDARY P.System Data
205
CT PRIMARY
206
CT SECONDARY
207
SystemStarpoint
210
U4 transformer
211
Uph / Udelta
212
Usy2 connection
214A
φ Usy2-Usy1
215
Usy1/Usy2 ratio
220
I4 transformer
221
I4/Iph CT
230
Rated Frequency
235
PHASE SEQ.
239
T-CB close
240A
TMin TRIP CMD
241A
TMax CLOSE CMD
242
T-CBtest-dead
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Function
C
Setting Options
P.System Data
towards Line
1
towards Busbar
P.System Data
1.0 .. 1200.0 kV
1
80 .. 125 V
1
P.System Data
10 .. 5000 A
1
P.System Data
1A
1
5A
P.System Data
Solid Earthed
1
Peterson-Coil
Isolated
P.System Data
Not connected
1
Udelta transf.
Usy2 transf.
Ux transformer
P.System Data
0.10 .. 9.99
1
P.System Data
L1-E
1
L2-E
L3-E
L1-L2
L2-L3
L3-L1
P.System Data
0 .. 360 °
1
P.System Data
0.50 .. 2.00
1
P.System Data
Not connected
1
In prot. line
P.System Data
0.010 .. 5.000
1
P.System Data
50 Hz
1
60 Hz
P.System Data
L1 L2 L3
1
L1 L3 L2
P.System Data
0.01 .. 0.60 sec
1
P.System Data
0.02 .. 30.00 sec
1
P.System Data
0.01 .. 30.00 sec
1
P.System Data
0.00 .. 30.00 sec
1
Functions, Settings, Information
Default Setting
Comments
towards Line
CT Starpoint
400.0 kV
Rated Primary Voltage
100 V
Rated Secondary Voltage
(Ph-Ph)
1000 A
CT Rated Primary Current
1A
CT Rated Secondary
Current
Solid Earthed
System Starpoint is
Not connected
U4 voltage transformer is
1.73
Matching ratio Phase-VT
To Open-Delta-VT
L1-L2
VT connection for Usy2
0 °
Angle adjustment Usy2-
Usy1
1.00
Matching ratio Usy1/Usy2
In prot. line
I4 current transformer is
1.000
Matching ratio I4/Iph for
CT's
50 Hz
Nominal Frequency
L1 L2 L3
Phase Sequence
0.06 sec
Closing (operating) time
of CB
0.10 sec
Minimum TRIP Command
Duration
0.10 sec
Maximum Close
Command Duration
0.10 sec
CB test: Dead time
E.2 Settings
297