The monitoring function can also be used for the display of negative active power. In this case the areas must
be defined as shown in
[wirkleistung-ind-kap--wlk040602, 1, en_GB]
Figure 2-57
The two angles must be at least 3° apart; if they are not, monitoring is blocked, and the indication
wrong (No. 132 is output.
The following conditions must be fulfilled for measurement to be enabled:
•
The positive sequence current Ι
•
The positive sequence voltage U
•
The angles set in address 2941 φA and 2942 φB must be at least 3° apart. Incorrect parameter settings
cause the indication 132
•
The "Fuse-Failure-Monitor" and the measured voltage failure monitoring must not have responded, and
binary input indication 361
If monitoring is not active, this fact is signaled by the indication
Figure 2-58
shows the logic of the positive sequence system phase angle monitoring.
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Figure 2-57
.
Phase Angle Monitoring for Negative Active Power
is higher than the value set in parameter 2943 I1>.
1
is higher than the value set in parameter 2944 U1>.
1
φ Set wrong to be output.
>FAIL:Feeder VT must not be present.
2.7 Monitoring Functions
φ(PQ Pos) block (No. 131).
Functions
φ Set
139