Siemens SIPROTEC 4 7VK61 Manual page 289

Breaker management device
Table of Contents

Advertisement

Addr. Parameter
1151
MAN. CLOSE
1152
Man.Clos. Imp.
2601
Operating Mode
2610
Iph>>
2611
T Iph>>
2612
3I0>> PICKUP
2613
T 3I0>>
2614
I>> InstTrip BI
2615
I>> SOTF
2620
Iph>
2621
T Iph>
2622
3I0>
2623
T 3I0>
2624
I> Telep/BI
2625
I> SOTF
2630
Iph> STUB
2631
T Iph STUB
2632
3I0> STUB
2633
T 3I0 STUB
2634
I-STUB Telep/BI
2635
I-STUB SOTF
2640
Ip>
2642
T Ip Time Dial
2643
Time Dial TD Ip
2646
T Ip Add
2650
3I0p PICKUP
2652
T 3I0p TimeDial
2653
TimeDial TD3I0p
2656
T 3I0p Add
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Function
C
Setting Options
P.System Data
with Sync-check
2
w/o Sync-check
NO
P.System Data
OBJVERWparaMEIN-
2
STELL
Back-Up O/C
ON
OFF
Back-Up O/C
1A
0.05 .. 50.00 A
5A
0.25 .. 250.00 A
Back-Up O/C
0.00 .. 30.00 sec
Back-Up O/C
1A
0.05 .. 25.00 A
5A
0.25 .. 125.00 A
Back-Up O/C
0.00 .. 30.00 sec
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
Back-Up O/C
1A
0.05 .. 50.00 A
5A
0.25 .. 250.00 A
Back-Up O/C
0.00 .. 30.00 sec
Back-Up O/C
1A
0.05 .. 25.00 A
5A
0.25 .. 125.00 A
Back-Up O/C
0.00 .. 30.00 sec
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
Back-Up O/C
1A
0.05 .. 50.00 A
5A
0.25 .. 250.00 A
Back-Up O/C
0.00 .. 30.00 sec
Back-Up O/C
1A
0.05 .. 25.00 A
5A
0.25 .. 125.00 A
Back-Up O/C
0.00 .. 30.00 sec
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
Back-Up O/C
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
Back-Up O/C
0.05 .. 3.00 sec
Back-Up O/C
0.50 .. 15.00
Back-Up O/C
0.00 .. 30.00 sec
Back-Up O/C
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
Back-Up O/C
0.05 .. 3.00 sec
Back-Up O/C
0.50 .. 15.00
Back-Up O/C
0.00 .. 30.00 sec
Functions, Settings, Information
Default Setting
Comments
NO
Manual CLOSE
COMMAND generation
none
MANUAL Closure Impulse
after CONTROL
ON
Operating mode
2.00 A
Iph>> Pickup
10.00 A
0.30 sec
T Iph>> Time delay
0.50 A
3I0>> Pickup
2.50 A
2.00 sec
T 3I0>> Time delay
YES
Instantaneous trip via BI
NO
Instantaneous trip after
SwitchOnToFault
1.50 A
Iph> Pickup
7.50 A
0.50 sec
T Iph> Time delay
0.20 A
3I0> Pickup
1.00 A
2.00 sec
T 3I0> Time delay
NO
Instantaneous trip via
Teleprot./BI
NO
Instantaneous trip after
SwitchOnToFault
1.50 A
Iph> STUB Pickup
7.50 A
0.30 sec
T Iph STUB Time delay
0.20 A
3I0> STUB Pickup
1.00 A
2.00 sec
T 3I0 STUB Time delay
NO
Instantaneous trip via
Teleprot./BI
NO
Instantaneous trip after
SwitchOnToFault
2147483647 A
Ip> Pickup
2147483647 A
0.50 sec
T Ip Time Dial
5.00
Time Dial TD Ip
0.00 sec
T Ip Additional Time Delay
2147483647 A
3I0p Pickup
2147483647 A
0.50 sec
T 3I0p Time Dial
5.00
Time Dial TD 3I0p
0.00 sec
T 3I0p Additional Time
Delay
E.2 Settings
289