E.2 Settings
Addr. Parameter
2652
T 3I0p TimeDial
2653
TimeDial TD3I0p
2656
T 3I0p Add
2660
IEC Curve
2661
ANSI Curve
2670
I(3I0)p Tele/BI
2671
I(3I0)p SOTF
2680
SOTF Time DELAY
2901
MEASURE. SUPERV Meas-
2902A BALANCE U-LIMIT
2903A BAL. FACTOR U
2904A BALANCE I LIMIT
2905A BAL. FACTOR I
2906A ΣI THRESHOLD
2907A ΣI FACTOR
2908A T BAL. U LIMIT
2909A T BAL. I LIMIT
2910
FUSE FAIL MON.
2911A FFM U>(min)
2912A FFM I< (max)
2913A FFM U<max (3ph)
300
Function
C
Setting Options
Back-Up O/C
0.05 .. 3.00 sec
Back-Up O/C
0.50 .. 15.00
Back-Up O/C
0.00 .. 30.00 sec
Back-Up O/C
Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Back-Up O/C
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
Back-Up O/C
0.00 .. 30.00 sec
ON
urem.Superv
OFF
Meas-
10 .. 100 V
urem.Superv
Meas-
0.58 .. 0.95
urem.Superv
Meas-
1A
0.10 .. 1.00 A
urem.Superv
5A
0.50 .. 5.00 A
Meas-
0.10 .. 0.95
urem.Superv
Meas-
1A
0.05 .. 2.00 A
urem.Superv
5A
0.25 .. 10.00 A
Meas-
0.00 .. 0.95
urem.Superv
Meas-
5 .. 100 sec
urem.Superv
Meas-
5 .. 100 sec
urem.Superv
Meas-
ON
urem.Superv
OFF
Meas-
10 .. 100 V
urem.Superv
Meas-
1A
0.10 .. 1.00 A
urem.Superv
5A
0.50 .. 5.00 A
Meas-
2 .. 100 V
urem.Superv
Default Setting
Comments
0.50 sec
3I0P: Inst time (IEC char-
acteristics) T 3I0P
5.00
3I0P: Inst time (ANSI
characteristics) D 3I0P
0.00 sec
3I0P: Inst additional delay
T 3I0delay
Normal Inverse
IEC Curve
Inverse
ANSI Curve
NO
Instantaneous trip via
Teleprot./BI
NO
Instantaneous trip after
SwitchOnToFault
0.00 sec
Delay time for switching
ON
Measurement Supervision
50 V
Symmetry V: 5A
0.75
Symmetry V: Slope of the
Characteristic Curve
0.50 A
Symmetry Iph: 5A
2.50 A
0.50
Symmetry Iph: Slope of
the Characteristic Curve
0.10 A
Sum I: 5A
0.50 A
0.10
Sum I: Slope of the Char-
acteristic Curve
5 sec
Symmetry Uph: Pickup
delay
5 sec
Symmetry Iph: Pickup
delay
ON
Operating mode for Fuse
Failure Monitor
30 V
Minimum Voltage
Threshold V
0.10 A
Maximum Current
Threshold I
0.50 A
15 V
Umess for Current
Threshold (3phase)
SIPROTEC 4, 7VK61, Manual