Siemens SIPROTEC 4 7VK61 Manual page 301

Breaker management device
Table of Contents

Advertisement

Addr. Parameter
2914A FFM Idelta (3p)
2915
V-Supervision
2916A T V-Supervision
2941
φA
2942
φB
2943
I1>
2944
U1>
3401
AUTO RECLOSE
3402
CB? 1.TRIP
3403
T-RECLAIM
3403
T-RECLAIM
3404
T-BLOCK MC
3406
EV. FLT. RECOG.
3407
EV. FLT. MODE
3408
T-Start MONITOR
3409
CB TIME OUT
3410
T RemoteClose
3411A T-DEAD EXT.
3425
AR w/ BackUpO/C
3430
AR TRIP 3pole
3431
DLC or RDT
3433
T-ACTION ADT
3434
T-MAX ADT
3435
ADT 1p allowed
3436
ADT CB? CLOSE
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Function
C
Setting Options
Meas-
1A
0.05 .. 1.00 A
urem.Superv
5A
0.25 .. 5.00 A
Meas-
w/ CURR.SUP
urem.Superv
w/ I> & CBaux
OFF
Meas-
0.00 .. 30.00 sec
urem.Superv
Meas-
0 .. 359 °
urem.Superv
Meas-
0 .. 359 °
urem.Superv
Meas-
1A
0.05 .. 2.00 A
urem.Superv
5A
0.25 .. 10.00 A
Meas-
2 .. 70 V
urem.Superv
Autoreclosure
OFF
ON
Autoreclosure
YES
NO
Autoreclosure
0.50 .. 300.00 sec
Autoreclosure
0.50 .. 300.00 sec
Autoreclosure
0.50 .. 300.00 sec
Autoreclosure
with PICKUP
with TRIP
Autoreclosure
blocks AR
starts 3p AR
Autoreclosure
0.01 .. 300.00 sec
Autoreclosure
0.01 .. 300.00 sec
Autoreclosure
0.00 .. 300.00 sec
Autoreclosure
0.50 .. 300.00 sec
Autoreclosure
YES
NO
Autoreclosure
YES
Autoreclosure
NO
Autoreclosure
WITHOUT
RDT
DLC
Autoreclosure
0.01 .. 300.00 sec
Autoreclosure
0.50 .. 3000.00 sec 5.00 sec
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Functions, Settings, Information
Default Setting
Comments
0.10 A
Delta Current Threshold
(3phase)
0.50 A
w/ CURR.SUP
Voltage Failure Supervi-
sion
3.00 sec
Delay Voltage Failure
Supervision
200 °
Limit setting PhiA
340 °
Limit setting PhiB
0.05 A
Minimum value I1>
0.25 A
20 V
Minimum value U1>
ON
Auto-Reclose function
NO
CB ready interrogation at
1st trip
3.00 sec
Reclaim time after
successful AR cycle
3.00 sec
Reclaim time after
successful AR cycle
1.00 sec
AR blocking duration after
manual close
with TRIP
Evolving fault recognition
starts 3p AR
Evolving fault (during the
dead time)
0.20 sec
AR start-signal monitoring
time
3.00 sec
Circuit Breaker (CB)
Supervision Time
2147483647 sec
Time until ON
2147483647 sec
Maximum dead time
extension
YES
AR with back-up overcur-
rent?
YES
3-pole trip (CB plausi-
bility)
WITHOUT
Dead Line Check or
Reduced Dead Time
0.20 sec
Action time
Maximum dead time
NO
1pole TRIP allowed?
NO
CB ready interrogation
before reclosing
E.2 Settings
301