Siemens SIPROTEC 4 7VK61 Manual page 111

Breaker management device
Table of Contents

Advertisement

Addr.
Parameter
3719A
Uphph>(>) RESET
3721
3U0>(>) (or Ux)
3722
3U0>
3723
T 3U0>
3724
3U0>>
3725
T 3U0>>
3728A
3U0>(>) Stabil.
3729A
3U0>(>) RESET
3731
U1>(>)
3732
U1>
3733
T U1>
3734
U1>>
3735
T U1>>
3739A
U1>(>) RESET
3741
U2>(>)
3742
U2>
3743
T U2>
3744
U2>>
3745
T U2>>
3749A
U2>(>) RESET
3751
Uph-e<(<)
3752
Uph-e<
3753
T Uph-e<
3754
Uph-e<<
3755
T Uph-e<<
3758
CURR.SUP. Uphe<
3759A
Uph-e<(<) RESET
3761
Uph-ph<(<)
3762
Uph-ph<
3763
T Uph-ph<
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Setting Options
0.30 .. 0.99
OFF
Alarm Only
ON
U>Alarm U>>Trip
1.0 .. 220.0 V
0.00 .. 100.00 sec
1.0 .. 220.0 V
0.00 .. 100.00 sec
ON
OFF
0.30 .. 0.99
OFF
Alarm Only
ON
U>Alarm U>>Trip
2.0 .. 220.0 V
0.00 .. 100.00 sec
2.0 .. 220.0 V
0.00 .. 100.00 sec
0.30 .. 0.99
OFF
Alarm Only
ON
U>Alarm U>>Trip
2.0 .. 220.0 V
0.00 .. 100.00 sec
2.0 .. 220.0 V
0.00 .. 100.00 sec
0.30 .. 0.99
OFF
Alarm Only
ON
U<Alarm U<<Trip
1.0 .. 100.0 V
0.00 .. 100.00 sec
1.0 .. 100.0 V
0.00 .. 100.00 sec
ON
OFF
1.01 .. 1.20
OFF
Alarm Only
ON
U<Alarm U<<Trip
1.0 .. 175.0 V
0.00 .. 100.00 sec
2.5 Under and over-voltage protection (optional)
Default Setting
Comments
0.98
Uph-ph>(>) Reset ratio
OFF
Operating mode 3U0 (or Ux) over-
voltage
30.0 V
3U0> Pickup (or Ux>)
2.00 sec
T 3U0> Time Delay (or T Ux>)
50.0 V
3U0>> Pickup (or Ux>>)
1.00 sec
T 3U0>> Time Delay (or T Ux>>)
ON
3U0>(>): Stabilization 3U0-Meas-
urement
0.95
3U0>(>) Reset ratio (or Ux)
OFF
Operating mode U1 overvoltage
prot.
150.0 V
U1> Pickup
2.00 sec
T U1> Time Delay
175.0 V
U1>> Pickup
1.00 sec
T U1>> Time Delay
0.98
U1>(>) Reset ratio
OFF
Operating mode U2 overvoltage
prot.
30.0 V
U2> Pickup
2.00 sec
T U2> Time Delay
50.0 V
U2>> Pickup
1.00 sec
T U2>> Time Delay
0.98
U2>(>) Reset ratio
OFF
Operating mode Uph-e under-
voltage prot.
30.0 V
Uph-e< Pickup
2.00 sec
T Uph-e< Time Delay
10.0 V
Uph-e<< Pickup
1.00 sec
T Uph-e<< Time Delay
ON
Current supervision (Uph-e)
1.05
Uph-e<(<) Reset ratio
OFF
Operating mode Uph-ph under-
voltage prot.
50.0 V
Uph-ph< Pickup
2.00 sec
T Uph-ph< Time Delay
Functions
111