Functions, Settings, Information
E.2 Settings
Addr. Parameter
3771
U1<(<)
3772
U1<
3773
T U1<
3774
U1<<
3775
T U1<<
3778
CURR.SUP.U1<
3779A U1<(<) RESET
3901
FCT BreakerFail
3902
I> BF
3903
1p-RETRIP (T1)
3904
T1-1pole
3905
T1-3pole
3906
T2
3907
T3-BkrDefective
3908
Trip BkrDefect.
3909
Chk BRK CONTACT
3912
3I0> BF
3913
T2StartCriteria
3921
End Flt. stage
3922
T-EndFault
3931
PoleDiscrepancy
3932
T-PoleDiscrep.
4001
FCT TripSuperv.
4002
No. of BI
4003
Alarm Delay
296
Function
C
Setting Options
Voltage Prot.
OFF
Alarm Only
ON
U<Alarm U<<Trip
Voltage Prot.
1.0 .. 100.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
1.0 .. 100.0 V
Voltage Prot.
0.00 .. 100.00 sec
Voltage Prot.
ON
OFF
Voltage Prot.
1.01 .. 1.20
Breaker Failure
ON
OFF
Breaker Failure 1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
Breaker Failure
NO
YES
Breaker Failure
0.00 .. 30.00 sec
Breaker Failure
0.00 .. 30.00 sec
Breaker Failure
0.00 .. 30.00 sec
Breaker Failure
0.00 .. 30.00 sec
Breaker Failure
NO
with T1-trip
with T2-trip
w/ T1/T2-trip
Breaker Failure
NO
YES
Breaker Failure 1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
Breaker Failure
With exp. of T1
Parallel withT1
Breaker Failure
ON
OFF
Breaker Failure
0.00 .. 30.00 sec
Breaker Failure
ON
OFF
Breaker Failure
0.00 .. 30.00 sec
TripCirc.Superv
ON
OFF
TripCirc.Superv
1 .. 2
TripCirc.Superv
1 .. 30 sec
Default Setting
Comments
OFF
Operating mode U1
undervoltage prot.
30.0 V
U1< Pickup
2.00 sec
T U1< Time Delay
10.0 V
U1<< Pickup
1.00 sec
T U1<< Time Delay
ON
Current supervision (U1)
1.05
U1<(<) Reset ratio
ON
Breaker Failure Protection
0.10 A
Pick-up threshold I>
0.50 A
YES
1pole retrip with stage T1
(local trip)
0.00 sec
T1, Delay after 1pole start
(local trip)
0.00 sec
T1, Delay after 3pole start
(local trip)
0.15 sec
T2, Delay of 2nd stage
(busbar trip)
0.00 sec
T3, Delay for start with
defective bkr.
NO
Trip output selection with
defective bkr
YES
Check Breaker contacts
0.10 A
Pick-up threshold 3I0>
0.50 A
Parallel withT1
T2 Start Criteria
OFF
End fault protection
2.00 sec
Trip delay of end fault
protection
OFF
Pole Discrepancy supervi-
sion
2.00 sec
Trip delay with pole
discrepancy
OFF
TRIP Circuit Supervision is
2
Number of Binary Inputs
per trip circuit
2 sec
Delay Time for alarm
SIPROTEC 4, 7VK61, Manual