Functions
2.7 Monitoring Functions
short transition periods. After clearance of the failure in the trip circuit, the failure alarm automatically resets
with the same time delay.
[logikdiagramm-auskruebrwchg-2-be-wlk-310702, 1, en_GB]
Figure 2-60
Supervision with One Binary Input
According to
Figure
the protection device. The circuit breaker auxiliary contact is bridged with a high-resistance bypass resistor R.
The control voltage for the circuit breaker should be at least twice as high as the minimum voltage drop at the
binary input (U
Ctrl
a system control voltage of over 38 V.
A calculation example for the bypass resistor R is shown in the configuration notes in Section "Mounting and
Connections", margin heading "Trip Circuit Supervision".
[prinzip-ausloesekrueb-1-be-wlk-010802, 1, en_GB]
Figure 2-61
TR
Trip relay contact
CB
Circuit breaker
TC
Circuit breaker trip coil
Aux1
Circuit breaker auxiliary contact (NO contact)
Aux2
Circuit breaker auxiliary contact (NC contact)
U-CTR
Control voltage for trip circuit
U-BI
Input voltage of binary input
R
Bypass resistor
UR
Voltage across the bypass resistor
During normal operation, the binary input is activated (logical condition "H") when the trip contact is open and
the trip circuit is intact, because the supervision circuit is closed either by the circuit breaker auxiliary contact
(if the circuit breaker is closed) or through the bypass resistor R. Only as long as the trip contact is closed, the
binary input is short-circuited and thereby deactivated (logical condition "L").
If the binary input is permanently deactivated during operation, an interruption in the trip circuit or a failure of
the (trip) control voltage can be assumed.
146
Logic diagram of the trip circuit supervision with two binary inputs
2-61, the binary input is connected in parallel to the respective command relay contact of
> 2·U
). Since at least 19 V are needed for the binary input, the monitor can be used with
BImin
Principle of the trip circuit supervision with one binary input
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018