Mounting and Commissioning
3.3 Commissioning
Circuit breaker is open. The feeder is isolated (zero voltage). The VTmcb's of both voltage transformer
circuits must be closed.
For the synchronism check the program AR OVERRIDE = YES (address 3519) is set; the other programs
(addresses 3515 to 3518) are set to NO.
Via binary input (No.2906
must release closing (message
(synchrocheck configured and enabled correctly, see Sections
Notes
and
Address 3519 AR OVERRIDE must be set to NO.
Then the circuit breaker is closed while the line isolator is open (see
formers therefore measure the same voltage.
The programAR SYNC-CHECK = YES (address 3515) is set for synchronism check.
Via binary input (No.2906
must release closing (message
[synchronkontrolle-messspannungen-250702-kn, 1, en_GB]
Figure 3-25
If not, first check whether one of the before named messages 2947
diff> is available in the spontaneous messages.
The indication
address 215 Usy1/Usy2 ratio and recalculate the adaptation factor, if necessary.
The indication
does not match the setting at address 212 Usy2 connection (see Section
When measuring across a transformer, address 214 φ Usy2-Usy1 must also be checked; this must
adapt the vector group (see
polarity of the voltage transformer terminals forU
The program AR Usy1>Usy2< = YES (address 3517) and AR SYNC-CHECK = YES (address 3515) is set
for synchronism check.
Open the VT mcb of the measuring point U
Via binary input (No.2906
If there is, the VT mcb for the measuring point U
state, alternatively check the binary input
Reclose the VT mcb of the measuring point U
Open the circuit breaker.
The program AR Usy1<Usy2> = YES (address 3516) and AR Usy1>Usy2< = NO (address 3517) is set
for synchronism check.
218
>Sync. Start AR ) initiate the measuring request. The synchronism check
Sync. release , No. 2951). If not, check all relevant parameters again
2.4.2 Setting
Notes).
>Sync. Start AR ) initiate the measuring request. The synchronism check
Sync. release , No.2951).
Measuring voltages for the synchrocheck — example
Sync. Udiff> indicates that the magnitude (ratio) adaptation is incorrect. Check
Sync. φ-diff> indicates that the phase relation, in this example of the busbar voltage,
Section2.1.3.1 Setting
>Sync. Start AR ) a measuring request is entered. There is no close release.
2.1.1.2 Setting
Figure
Sync. Udiff> or 2949 Sync. φ-
Notes). If these are correct, there is probably a reverse
.
sy2
(No. 362
>FAIL:U4 VT ).
sy2
is not allocated. Check whether this is the required
sy2
>FAIL:U4 VT (No. 362).
.
sy2
Notes,
2.1.3.1 Setting
3-25). Both voltage trans-
2.1.3.1 Setting
Notes).
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018