Mounting and Commissioning
3.1 Mounting and Connections
Jumper
X73
Input/Output Board C-I/O-2 Release 7VK61 ../ or HigherFF
The nominal current or measuring range settings are checked on the input/output board C-I/O-2.
[ein-ausgabebgr-c-io-2-ab-ausgabe7-251103-oz, 1, en_GB]
Figure 3-9
Table 3-12
Jumper
X51
192
Mounting location
2-3 (L)
Input/output module C-I/O-2 up to release 7VK61**.../FF, with representation of the jumper
settings required for checking the configuration settings
Jumper setting for Nominal Current or Measuring Range
Nominal current 1 A
Measuring range 100 A
1-2
Nominal current 5 A
Measuring range 500 A
1-2
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018