Information List; Process Data; Functional Description - Siemens SIPROTEC 4 7VK61 Manual

Breaker management device
Table of Contents

Advertisement

Functions
2.10 Command Processing
2.10.2.2

Information List

No.
Information
-
Breaker
-
Breaker
-
Disc.Swit.
-
Disc.Swit.
-
EarthSwit
-
EarthSwit
-
Brk Open
-
Brk Close
-
Disc.Open
-
Disc.Close
-
E Sw Open
-
E Sw Cl.
-
Q2 Op/Cl
-
Q2 Op/Cl
-
Q9 Op/Cl
-
Q9 Op/Cl
-
Fan ON/OFF
-
Fan ON/OFF
31000
Q0 OpCnt=
31001
Q1 OpCnt=
31002
Q2 OpCnt=
31008
Q8 OpCnt=
31009
Q9 OpCnt=

Process Data

2.10.3
During the processing of commands, independently of the further allocation and processing of indications,
command and process feedbacks are sent to the indication processing. These indications contain information
on the cause. With the corresponding allocation (configuration) these indications are entered in the event log,
thus serving as a report.
A listing of possible operational indications and their meaning, as well as the command types needed for trip-
ping and closing the switchgear or for raising and lowering transformer taps and detailed information are
described in the SIPROTEC 4 System Description.
2.10.3.1

Functional Description

Acknowledgement of Commands to the Device Front
All indications with the source of command LOCAL are transformed into a corresponding response and shown
in the display of the device.
Acknowledgement of commands to local/remote/DIGSI
The acknowledgement of indications which relate to commands with the origin "Command Issued = Local/
Remote/DIGSI" are sent back to the initiating point independent of the routing (configuration on the serial
digital interface).
The acknowledgement of commands is therefore not executed by a response indication as it is done with the
local command but by ordinary command and feedback information recording.
174
Type of
Comments
Informa-
tion
CF_D12
Breaker
DP
Breaker
CF_D2
Disconnect Switch
DP
Disconnect Switch
CF_D2
Earth Switch
DP
Earth Switch
IntSP
Interlocking: Breaker Open
IntSP
Interlocking: Breaker Close
IntSP
Interlocking: Disconnect switch Open
IntSP
Interlocking: Disconnect switch Close
IntSP
Interlocking: Earth switch Open
IntSP
Interlocking: Earth switch Close
CF_D2
Q2 Open/Close
DP
Q2 Open/Close
CF_D2
Q9 Open/Close
DP
Q9 Open/Close
CF_D2
Fan ON/OFF
DP
Fan ON/OFF
VI
Q0 operationcounter=
VI
Q1 operationcounter=
VI
Q2 operationcounter=
VI
Q8 operationcounter=
VI
Q9 operationcounter=
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents