Functions
2.2 Device
Note
Setting address 610 FltDisp.LED/LCD to (Target on TRIP) is only reasonable if address 615 T MIN
LED HOLD is set to 0.
Figure 2-3
Default display of a 4-line display
After startup of the device featuring a 4-line display, measured values are displayed by default. The arrow keys
on the device front allow different displays of the measured values to be selected for the so-called default dis-
play. The start image of the default display, which is displayed by default after startup of the device, can be
selected via parameter 640 Start image DD. The available representation types for the measured value are
listed in the Appendix.
2.2.2

Settings

Addr.
Parameter
610
FltDisp.LED/LCD
611
Spont. FltDisp.
615
T MIN LED HOLD
640
Start image DD
40
Creation of the resetting command for stored LEDs / relays
Setting Options
Target on PU
Target on TRIP
YES
NO
0 .. 60 min
image 1
image 2
image 3
image 4
Default Setting
Target on PU
Fault Display on LED / LCD
NO
Spontaneous display of flt.annun-
ciations
5 min
Minimum hold time of lachted
LEDs
image 1
Start image Default Display
C53000-G1176-C149-7, Release date 03.2010
Comments
SIPROTEC, 7UM62, Manual