KEB COMBIVERT F5 Instructions For Use Manual page 58

Installation f5 profinet operator
Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

PARAMETER DEScRIPTION
ID:
Name:
Meaning
Parameter number (PNU):
Subindex:
Data type:
Coding:
Standard value:
Note:
58
Fb33
Pnet_PDIN_Config
Specifies the required PROFINET PDIN configuration
02A1h
0
Uint32
b31...b24
b23...b16
Module-Id
Submodule-Id
00000000h: ‚Not used', setting in accordance with Fb10
80400002h: ‚1x16BitIn'
80410004h: ‚2x16BitIn'
80420006h: ‚3x16BitIn'
02010008h: ‚4x16BitIn'(*1)
8044000Ah: ‚5x16BitIn'
8045000Ch: ‚6x16BitIn'
8046000Eh: ‚7x16BitIn
04030010h: ‚8x16BitIn'(*1)
(*1): These values are downward compatible and offer the possibility to use
the new parameter Fb33 with an 'old' GSDML.
0: Setting in accordance with Fb11
A changed value is immediately stored non-volatile, but it becomes active
only at the next switch on. If bit 5 of parameter Fb01 FBS Config is set, only
the value compatible with the process data length of the set PD mapping can
be adjusted in parameter Fb33. However, deactivating of parameter Fb33
(value = 0) is always possible.
b15...b8
b7...b0
reserved
Pd-length