DIFFERENcES bETWEEN NORMAL AND SyNcHRONOUS MODE
The name can be changed by the master via service ‚DCP set'. Then this name is
non-volatile stored. With next power on the PROFINET slave logs in with the stored
name, if NodeSwitchVal > = 240 and no special configuration is selected (see below).
The maximum supported length of the PROFINET name is currently 128 digits.
The range for switch positions >= 240 is used in software versions up to V3.1 exclusively
to activate the non-volatile stored name.
This value range is also used for special configurations from software V3.2. The function
of the values 240 and 255 remains unchanged for downward compatibility with older
software versions. The following table shows all values and their meaning (software
version V3.2):
NodeSwitchVal
0...239
240
241
242
243
244...253
254
255
Short text
Description
FixedName
PROFINET-Name = ‚kebf5-n' with ‚n' the deci-
mal value of the node switch (see above)
UseSavedNoS
Use the last stored as PROFINET name
ResetToDefault
Set all non-volatile values to default:
•
PROFINET-Name = ‚'
•
PROFINET-Ip-Addr = 0.0.0.0
•
PROFINET-Ip-Mask = 0.0.0.0
•
PROFINET-Ip-Gateway = 0.0.0.0
EmptyPnet
(Only) reset of the PROFINET addressing:
•
PROFINET-Name = ‚'
•
PROFINET-Ip-Addr = 0.0.0.0
•
PROFINET-Ip-Mask = 0.0.0.0
•
PROFINET-Ip-Gateway = 0.0.0.0
EmptyIP
(Only) reset of the PROFINET-IP addressing:
•
PROFINET-Name = last stored value
•
PROFINET-Ip-Addr = 0.0.0.0
•
PROFINET-Ip-Mask = 0.0.0.0
•
PROFINET-Ip-Gateway = 0.0.0.0
Reserved
These values are reserved for future special
configurations
KEBProdTest
Special configuration for KEB production test:
•
PROFINET-Name = ‚'
•
PROFINET-Ip-Addr = 192.168.0.100
•
PROFINET-Ip-Mask = 255.255.255.0
•
PROFINET-Ip-Gateway = 0.0.0.0
UseSavedNoS
Use the last stored as PROFINET name
29