PROFINET AcycLIc DATA (PARAMETER cHANNEL) AccORDING TO PROFIDRIVE
Parameter request:
Block-Definition
Request Header
1st parameter address
:
n th parameter address
1st parameter value(s)
:
Nth parameter value(s)
The parameter values are only contained in a request with request ID = 2.
Request Reference: 1 ... FFh: Serial number for differentiation of the different requests
Request ID:
Axis-No. = 0, since the F5 PROFINET operator represents an 1:1 gateway.
No. of parameters: 1...39 (max. 39 parameters can be read or written via request)
Attribute:
Byte n
Request Reference
Axis-No.
Attribute
Parameter Number (PNU)
Subindex
:
Attribute
Parameter Number (PNU)
Subindex
Format
Values
:
Value
01h
02h
Value
10h
20h
30h
Byte n+1
Request ID
No. of parameters = n
No. of elements
No. of elements
No. of values
Request parameter (Read)
Change parameter (Write)
Description (not supported here)
Text (not supported here)
n
0
2
4
6
8
:
4 + 6 x (n-1)
4 + 6 x n
:
Meaning
Meaning
Value