[Factory Setting]
Parameter
P251
AO1 Output Function
(0 to 10)V
P252
AO1 Analog Output
gain
P253
AO2 Analog Ouput
Function
(0 to 20)mA or
(4 to 20)mA
P254
AO2 Analog Output
Gain
P255
AO2 Analog Output
Type (0 to 20)mA or
(4 to 20)mA
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Range
Unit
Description / Notes
"JOG Only"
This option allows the slow speed with Jog in both forward and reverse
directions without auxiliary contactors connected at the input power
supply.
See more information and the notes at the P510 and P511 parameters.
U(V)
P511
0
Check possible options in table 6.24 and Figure 6.15.
0 to 10
For the values shown in Table 6.24, P252=1000 and AO1=10V.
[ 0=Not used ]
-
Sets the gain of the analog output AO1.
0.000 to 9.999
For P252=1.000 the value of output AO1 is set according to the
[ 1.000 ]
-
description in Figure 6.15.
Check the possible options in Table 6.24 and Figure 6.15.
0 to 10
For the values shown in Table 6.24, P253=2, P254=1000 and
[ 0=Not Used ]
-
AO2=20mA.
Sets the gain of the analog output AO2.
0.000 to 9.999
For P254=1.000 the value of output AO2 é is set according to the
[ 1.000 ]
description in Figure 6.15.
0.001
It selects the signal type of the current analog output AO2.
0 or 1
[ 0=0-20mA ]
-
For transforming the current analog output AO2 to a voltage output of
0 to 10V, connect a resistor of 500 ± 1% 0.5W in parallel with the
output signal a resistor of 500 ± 1% 0.5W.
Remember when the output type is selected to 4 to 20mA, this will be
the total range of the signal output.
0% of the signal = 4mA and 100% of the signal = 20mA.
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
P102
Figure 6.14 - Motor direction of rotation with "Jog only"
P255
0
1
Table 6.23 - AO2 signal type
P102
t(s)
P511
Output type
(0 to 20)mA
(4 to 20)mA
99