CHAPTER 3 - INSTALLATION AND CONNECTION
3.2.7
Fan Connections
44
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Grounding bar
Internal to the Panel
Figure 3.14 - Grounding connections for more than one
EMI – Electromagnetic interference:
The Soft-Starter SSW-06 is developed to be used in industrial systems
(Class A) as per Norm EN60947-4-2.
It's necessary to have a distance of 0,25m (10in) between the Soft-
Starter SSW-06 and the cables between the Soft-Starter SSW-07 and
the motor. Example: PLC wiring, temperature controllers, thermocouple
cables, etc.
Grounding the motor frame:
Always ground the motor frame. Ground the motor in the panel where
the Soft-Starter SSW-06 is installed. The Soft-Starter SSW-06 output
wiring to the motor must be laid separately from the input wiring, as
well as from the control and signal cables.
Available in models 255A to 820A. The rated voltage of the fans can
also be selected.
ATTENTION!
SELECT THE FAN VOLTAGE IN ACCORDANCE
WITH THE VOLTAGE APPLIED TO THE
TERMINALS X1:33 AND X1:34
ATENCION!
SELECCIONAR LA TENSION DE LOS VENTILADORES
DE ACUERDO CON LA TENSION APLICADA A LOS
BORNES X1:33 Y X1:34
ATENÇÃO!
SELECIONE A TENSÃO DOS VENTILADORES
DE ACORDO COM A TENSÃO APLICADA AOS
BORNES X1:33 E X1:34
X1E
Figura 3.15 – Selection of the Fan Voltage
Connector X1E pins 33 and 34. More details see figure 3.16.
Grounding bar
Internal to the Panel
Soft-Starter SSW-06
SELEÇÃO
Voltage Selection
DE TENSÃO
110/220V
110/220V
Fan
ALIMENTAÇÃO
Fan Power Supply
VENTILADOR