Parameter
6.7 PROTECTIONS PARAMETERS - P600 to P699
P600
(1)
Intermediate
Undervoltage
(1)
P601
Time of Immediate
Undervoltage
P602
(1)
Intermediate
Overvoltage
(1)
P603
Time of Immediate
Overvoltage
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Range
[Factory Setting]
Unit
Description / Notes
P523
P110
P111
The under and overvoltage are setting as percentage of the motor
0 to 30
rated voltage (P400).
[ 20 ]
P600 sets the minimum voltage level at which the motor can operate
1 %Un of the Motor
without problems. This protection function acts when the line voltage
drops to a value lower than the set and is present during a time equal
1 to 99
to or longer than those set at P601. If this condition is present, the
[ 1 ]
Soft-Starter is disabled and an Undervoltage Error is displayed.
1s
P602 sets the maximum overvoltage level that the motor allows, during
the time that has been set at P603. If this time is exceeded, the
0 to 20
Soft-Starter is disabled and an Overvoltage Error is displayed.
[ 15 ]
1 %Un of the Motor
1 to 99
[ 1 ]
U(V)
1s
P602
P600
U(V)
P602
P600
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
I(A)
Start
I Limit
0
P112
P521
P102
Maximum Time
Enable
Current Ramp
Figure 6.22 - Actuation Levels of the Starting Torque Pulse.
NOTE!
These functions are active the entire time the motor is running.
Actuation Region
Running
Nominal
0
Enable
Fault
Action
Nominal
Under
Voltage
t0
P601
Figura 6.23 - Actuation Levels in case of Undervoltage and Overvoltage
I Rated Current
Deceleration
ramp
Disable
U (V)
Over
Voltage
Nominal
t1(s) t0
P603
t(s)
Disable
t(s)
Fault
Action
t1(s)
113