WEG SSW-06.0205 User Manual page 10

Ssw-06 series.
Table of Contents

Advertisement

SSW-06 - QUICK PARAMETER REFERENCE
Parameter
Description
P042
Time Powered
P043
Time Enabled
P050
Motor Thermal Protection Status
P085
Fieldbus Communication Board Status
REGULATION PARAMETERS P100 TO P199
Voltage Ramp
P101
Initial Voltage (% Un of the motor)
P102
Acceleration Ramp Time
P103
Deceleration Voltage Step
(% Un of the motor)
P104
Deceleration Ramp Time
P105
End Deceleration Voltage
(% Un of the Motor)
Current Limit
P110
Current Limit
(%In of the Motor current)
P111
Initial Current for the Current Ramp
(% In of the Motor)
P112
Time for the Current Ramp
(% of P102)
Torque Control
P120
(1)
Starting Torque Characteristics
P121
Initial Starting Torque (% Tn of Motor)
P122
End Starting Torque (% Tn of Motor)
P123
Minimum Starting Torque
(% Tn of the Motor)
P124
Time for the Minimum Start Torque
(% of P102)
P125
(1)
Stopping Torque Characteristics
P126
End Stop Torque (% Tn of the Motor)
P127
Minimum Stop Torque
(% Tn of the Motor)
P128
Time for the Minimum Stop Torque
(% of P104)
Pump Control
(1)
P130
Pump Control
By-pass
P140
(1)
External By-pass Contactor
10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Adjustable Range
0 to 65530
0 to 6553
0 to 250
0=Off
1=Board Inactive
2=Board Active and Offline
3=Board Active and Online
25 to 90
1 to 999
100=Inactive
99 to 60
0=Inactive
1 to 299
30 to 55
150 to 500
150 to 500
1 to 99
1=Constant
2=Linear
3=Quadratic
10 to 400
10 to 400
10 to 400
1 to 99
1=Constant
2=Linear
3=Quadratic
10 to 100
10 to 100
1 to 99
0= Pump I
1= Pump II
0=Inactive
1=Active
Factory
Unit
Setting
-
h
-
h
-
%
-
-
30
%
20
s
100=Inactive
%
0=Inactive
s
30
%
300
%
150
%
20
%
1=Constant
-
30
%
110
%
27
%
20
%
1=Constant
-
20
%
50
%
50
%
0= Pump I
-
0=Inactive
-
User´s
Page
Setting
81
82
82
82
82
83
84
84
84
84
85
85
86
87
87
87
87
88
88
89
89
89
89

Hide quick links:

Advertisement

Table of Contents
loading