CHAPTER 7 - APPLICATIONS AND PROGRAMMING
Pump
Control
P130
P101
P102
P103
P104
P105
P400
P401
P610
P611
P620
P406
P640
128
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Figure 7.9 – Manometer showing the pressure drop
9) Generally, the current increases at the end of the deceleration ramp
and in this case the motor requires more torque to achieve a smooth
water flow stop. When the motor has already stopped, but is still
enabled, the current will increase too much. To prevent this condition,
set P105 to a value that as soon it stoop it is also disabled;
10)Set P610 and P611 to current and time levels that prevent the
hydraulic pump from running without a load.
U(V)
Start
P101
0
P102
Enable
Pump Control
Figure 7.10 – Start with pump control
NOTES!
1) P400 and P401 must be set according to the line voltage and the
rated current of the used motor used;
2) If the hydraulic piping is not fitted with manometer, the hydraulic
rams can be noted at the pressure relief valves;
3) Please consider, that sudden line voltage drops results in motor
torque drops. Thus, ensure that the power supply line characteristics
are within the characteristics required for motor operation;
4) If errors are detected during the motor start, check all connections
of the Soft-Starter to the power line, the motor connections, the
voltage levels of the power line, the fuses, circuit-breakers and
disconnecting switches.
U(V)
100%Un
Stop
P103
0
P104
Disable
Stop
100%Un
P103
P104
Disable
P105
t(s)
P105
t(s)