Parameter
P007
Soft-Starter SSW-06
Output Voltage
P008
Power Factor
P009
Motor Torque
P010
Ouput Power
P011
Apparent Output
Power
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Range
[Factory Setting]
Unit
Description / Notes
Indicates the average True rms voltage of the tree output phases of
0 to 999
[ - ]
the Soft-Starter SSW-06 in Volts (V).
Accuracy: ± 2V.
1V
Indicates motor power factor.
0 to 1.00
Accuracy:
[ - ]
-
Indicates the motor torque in percent of the rated motor toque
0 to 999.9
[ - ]
(% Tn of the Motor).
The Soft-Starter SSW-06 is fitted with a software for estimating the
0,1%
motor torque by using the same principles contained in Weg
Frequency Inverter
This high technology software enables indicating the motor torque
very close to the effective present torque.
Accuracy of ± 10% Tn of the Motor.
Indicates the active power as average of the three ouput phases of the
0 to 6553.5
Soft-Starter SSW-06 in kilo Watts (kW).
[ - ]
0.1kW
Indicates the apparent power as average of the three ouput phases of
0 to 6553.5
[ - ]
the Soft-Starter SSW-06 in kilo Volts Ampere (kVA).
0.1kVA
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
± 5%.
:
NOTE!
The motor power factor will only be indicated when the current is at
20% of the rated current of the SSW-06.
0.00 (Zero) will be indicated if the current is below 20% of the
SSW-06 rated current.
ATTENTION!
Information related to the rated torque of the motor and maximum
starting torque of the motor can be found in the manufacturer's
catalogue.
NOTE!
For the correct torque to be indicated, in P009, all the parameters
related to the motor, P400 to P406, must be correctly programmed
according to the data informed in the motor name plate.
NOTE!
The output power will only be indicated when the current is greater
than 20% of the SSW-06 rated current.
0 (Zero) Will be indicated if the current is lower than 20% of the
SSW-06 rated current.
79