3.2.4
Connection of the Power
Supply to the Soft-Starter
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CHAPTER 3 - INSTALLATION AND CONNECTION
Current
Line
Model
100% In
Cables
(A)
(mm²)
SSW-06.0085
147
70
SSW-06.0130
225
95
SSW-06.0170
294
150
SSW-06.0205
355
185
SSW-06.0255
441
300
SSW-06.0312
540
400
SSW-06.0365
631
500
SSW-06.0412
713
2 x 185
SSW-06.0480
831
2 x 240
SSW-06.0604
1046
4 x 120
SSW-06.0670
1160
4 x 150
SSW-06.0820
1420
4 x 185
SSW-06.0950
1645
4 x 240
SSW-06.1100
1905
4 x 300
SSW-06.1400
2424
4 x 500
Table 3.7 - Recommended cables for inside delta motor connection
DANGER!
The AC input voltage must be compatible with the Soft-Starter SSW-06
rated voltage.
DANGER!
Provide power supply disconnecting switch. This disconnecting switch
must disconnect the AC input voltage from the Soft-Starter SSW-06,
always when required (for instance during maintenance services).
DANGER!
If a disconnect switch or a contactor is inserted in the motor supply
line, DO NOT operate these devices with running motor or when
Soft-Starter SSW-06 is enabled.
ATTENTION!
Control of overvoltage in the line that supplies the Soft-Starter must be
made using surge protection with a voltage of 680 Vac (phase to phase
connection) and energy absorption capacity of 40 joules (for models
from 85A to 205A) or 80 joules (for models from 255A to 1400A).
NOTE!
Use wire sizing and fuses as recommended in Table 3.6, 3.7 and 3.9.
The connector tightening torque is as indicated in Table 3.5. Use 70ºC
(158ºF) copper wires only.
Line
Motor
Motor
Bus
Cables
Bus
(mm x mm)
(mm²)
(mm x mm)
20 x 3
25
12 x 2
20 x 3
50
20 x 3
25 x 5
70
20 x 3
25 x 5
95
20 x 3
30 x 5
120
25 x 5
40 x 5
185
25 x 5
60 x 5
240
25 x 5
40x10
240
30x5
40x10
300
40x5
50x10
2 x 150
40x5
60x10
2 x 185
40x10
80x10
2 x 240
40x10
100x10
2 x 300
50x10
120x10
4 x 150
60x10
160x10
4 x 185
80x10
Grounding
Cables
(mm²)
10
25
35
50
70
95
120
120
150
150
185
240
300
2 x 150
2 x 185
39