CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Parameter
P012
Digital Input Status
DI1 to DI6
P013
Digital Outputs
RL1 to RL3 Status
80
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Range
[Factory Setting]
Unit
Description / Notes
 Indicates on the keypad LCD display the status of the 6 digital inputs
LCD=1,0
of the control board (DI1 to DI6). Number 1 stands for Active and Number
LED=0 to 255
0 for Inactive, in the following order: DI1, DI2,...,DI5, DI6.
[ - ]
 The LED Display shows a decimal value corresponding to the status
-
of the 6 digital inputs, where the status of each bit is considered one
bit in the specified sequence:
Inactive=0
Active=1
DI1 status is the most significant bit.
Example:
Dl1 = Active (+24V);
Dl2 = Inactive (0V);
Dl3 = Inactive (0V);
It is equivalent to the bit sequence:
10010000
Which corresponds to the decimal number 144.
The least significant bits are not displayed.
The keypad displays will be as follows:
DI1...DI6 Status
P012=100100
 Indicates on the keypad LCD display the status of the 3 relay outputs
LCD=1,0
LED=0 to 255
of the control board. Number 1 stands for Active and 0 for Inactive, in
[ - ]
the following order:
-
RL1, RL2, RL3.
 The keypad LED display shows the decimal value that corresponds to
the status of the 3 digital outputs, where the status of each bit is
considered one bit in the specified sequence:
Inactive=0
Active=1
RL1 status is the most significant bit.
The 5 least significant bits are always '0'.
Example:
RL1=Active; RL2=Inactive; RL3=Active
This is equivalent to the binary sequence:
10100000
Which corresponds to the decimal number 160.
The least significant bits are not displayed.
The Keypad displays will be:
RL1...RL3 Status
P012=101
Dl4 = Active (+24V);
Dl5 = Inactive (0V);
Dl6 = Inactive (0V).