WEG SSW-06.0205 User Manual page 95

Ssw-06 series.
Table of Contents

Advertisement

CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Parameter
P215
(1)
Copy Function (HMI)
96
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Range
[Factory Setting]
Unit
Description / Notes
 The copy function is used to transfer the content of the parameters
0 to 2
from one Soft-Starter SSW-06 to another. The Soft-Starters must be
[ 0=Off ]
-
of the same type (voltage/current) and the same software version must
be installed.
P215
Procedures:
1. Connect the Keypad to the Soft-Starter SSW-06 from which the
parameters will be copied (Soft-Starter A);
2. Set P215=1 (copy) for transferring the parameter from the Soft-Starter A
to the HMI. Press the key
the display will show COPY. P215 resets automatically to 0 (Inactive)
after the transfer has been completed.
3. Disconnect the keypad (HMI)from the Soft-Starter SSW-06.
4. Connect the same Keypad to the Soft-Starter SSW-06 to which the
parameters should be transferred (Soft-Starter B).
5. Set P215=2 (paste) for transferring the content from the non-volatile
keypad memory (EEPROM containing the parameter of the
Soft-Starter A) to the Soft-Starter B. Press the key
keypad is executing the copy function, the display shows COPY.
When P215 returns to 0, the parameter transfer has been concluded.
Now Soft-Starters A and B have the same parameter content.
Please remember:
If Soft-Starters A and B command different motors, please check the
motor parameters of Soft-Starter B.
For copying the parameter contents from Soft-Starter A to other
Soft-Starter, repeat procedures 4 and 5 above.
Figure 6.12 - Parameter Copying from "Soft-Starter A" to "Soft-Starter B"
Action
Explanation
0
Off
1
Copy
Transfers the current parameter contents from the
SSW  HMI
Soft-Starter and from Users 1/2 to the non volatile (HMI)
keypad memory (EEPROM). The current Soft-Starter
parameters are not changed.
2
Paste
Transfers the contents of the non-volatile (HMI) keypad
HMI  SSW
memory (EEPROM) to the current Soft-Starter SSW-06
parameters and to user 1 or 2 memories.
Table 6.19 - Copy function
Soft-Starter
A
Parameters
SSW HMI (copy)
P215=1
Press.
EEPROM
HMI
-
. While copy function is being executed,
Soft-Starter
B
Parameters
HMI SSW(paste)
P215=2
Press.
EEPROM
HMI
. While the

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents