CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Parameter
P125
(1)
Stopping Torque
Characteristics
P126
End Torque
for the Stop
1% Tn of the Motor
88
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Range
[Factory Setting]
Unit
Description / Notes
1 to 3
[ 1=constant]
-
 Here you can choose the torque limit profile that the
Soft-Starter SSW-06 shall supply to the motor during the start.
 Three different types of torque profiles are available that permit
improving the speed performance during the start process.
Tn(%)
 Here you can program the end torque limit or constant for the stop,
10 to 100
[ 20 ]
according to the torque type selected at P125.
 For more details about programming and application, refer to Torque
Control at P202.
P125
Stop torque profile
1
Constant (1 set point)
2
Linear (2 set points)
3
Quadratic (3 set points)
Table 6.7 - Stop Torque Characteristics
Stop
Tn Nominal
P125=1
P126
0
P128
P104
Tn(%)
0
Figure 6.8 – Available torque profiles for the stop process
NOTE!
Choose the type of torque control, easier to program and set,
according to the knowledge about the characteristics of the load.
P126
1 (Constant)
P126 limits the maximum torque during the stop process
2 (Linear)
P126 limits the end torque during the stop process
3 (Quadratic)
P126 limits the end torque during the stop process
Table 6.8 - Function of P126 according to P125
Tn(%)
Stop
Tn Nominal
P127
P126
0
t(s)
P128
P104
100%Tn
Tn Nominal
P125=3
P127
t(s)
P128
P104
Action
P125=2
P126
t(s)
P126