Parameter
P014
Last Fault
P015
Second Previous
Fault
P016
Third Previous
Fault
P017
Fourth Previous
Fault
P023
Software Version
P030
Current of Phase R
P031
Current of Phase S
P032
Current of Phase T
P033
Line Voltage - R-S
P034
Line Voltage - S-T
P035
Line Voltage - T-R
P042
Time Powered
LED: 0 to 6553h (x10)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Range
[Factory Setting]
Unit
Description / Notes
 Indicate the code of the last, second, third and fourth previous Faults.
03 to 77
 Fault Sequence:
[ - ]
Exy  P014  P015  P016  P017
-
03 to 77
[ - ]
-
03 to 77
[ - ]
-
03 to 77
[ - ]
-
 Indicates the Software Version contained in the microcontroller memory
X.XX
of the control board.
[ - ]
-
 Accuracy: ± 2% for full scale (full scale is 5 x In of the SSW-06).
0 to 9999.9
[ - ]
0.1A
0 to 9999.9
[ - ]
0.1A
0 to 9999.9
[ - ]
0.1A
 Accuracy: ± 2V.
0 to 999
[ - ]
1V
0 to 999
[ - ]
1V
0 to 999
[ - ]
1V
 Indicates the total number of hours that the Soft-Starter was powered.
LCD: 0 to 65530
 The LED Display shows the total number of hours that the
Soft-Starter was energized divided by 10.
[ - ]
 This value remains stored even when the Soft-Starter is switched OFF.
1h
Example: Indication of 22 hours powered.
Time Powered
P042=22h
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
NOTE!
When the connection is used inside the delta of the motor
(P150=1), the indication of the current value will already be
multiplied by 1.73.
NOTE!
The voltage will only be indicated when it reaches a value greater
than 15V.
Below this value, only 0.00 (zero) will be indicated.