Parameter
P111
Initial Current by
Current Ramp
1% Un of the Motor
P112
Time for Current
Ramp
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Range
[Factory Setting]
Unit
Description / Notes
Used for the control by Current Ramp, P202=4.
150 to 500
Allows a current limit ramp to be programmed to help in the starting
[ 150 ]
of loads that have a lower or higher starting torque.
The initial value of the current limit is shown by P111, the final value
is shown by P110 and the time is shown by P112, according to figure
6.6.
Used for the control by Current Ramp, P202=4.
1 to 99
It enables programming the time, in percent of P102, for the end
[ 20 ]
1% of P102
Current Ramp.
After the time, programmed at P112, has elapsed, it starts operation
by Current Limit, given by P110.
a)
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
I(A)
Start
I Limit
P110
Maximum Time
0
P102
Enable
Current Limit
Figure 6.5 – Fixed starting Current Limit
I(A)
Start
P110
I Limit
P111
0
P112
P102
Maximum Time
Enable
Current Limit
Rated Current
t(s)
Disable
Rated Current
t(s)
Disable
85