WEG SSW-06.0205 User Manual page 84

Ssw-06 series.
Table of Contents

Advertisement

Parameter
P111
Initial Current by
Current Ramp
1% Un of the Motor
P112
Time for Current
Ramp
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Range
[Factory Setting]
Unit
Description / Notes
 Used for the control by Current Ramp, P202=4.
150 to 500
 Allows a current limit ramp to be programmed to help in the starting
[ 150 ]
of loads that have a lower or higher starting torque.
 The initial value of the current limit is shown by P111, the final value
is shown by P110 and the time is shown by P112, according to figure
6.6.
 Used for the control by Current Ramp, P202=4.
1 to 99
 It enables programming the time, in percent of P102, for the end
[ 20 ]
1% of P102
Current Ramp.
 After the time, programmed at P112, has elapsed, it starts operation
by Current Limit, given by P110.
a)
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
I(A)
Start
I Limit
P110
Maximum Time
0
P102
Enable
Current Limit
Figure 6.5 – Fixed starting Current Limit
I(A)
Start
P110
I Limit
P111
0
P112
P102
Maximum Time
Enable
Current Limit
Rated Current
t(s)
Disable
Rated Current
t(s)
Disable
85