Parameter
P102
Acceleration
Ramp Time
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Range
[Factory Setting]
Unit
Description / Notes
 When the Soft-Starter SSW-06 has been programmed to Voltage
1 to 999
[ 20 ]
Ramp Control or Pump Control, this will be the ramp time of the
1s
voltage increment as shown in Figure 6.2.
 When the Soft-Starter SSW-06 has been programmed to Current
Limit control, Torque Control or Current Ramp, this time acts as
maximum starting time, as a protection against locked rotor.
P110
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
NOTE!
When another control type is selected, not the Voltage Ramp
or Pump Control, the initial voltage will be attenuated due to the
limit imposed by the current.
U(V)
Start
P101
0
P102
Enable
Voltage Ramp
Figure 6.2 – Acceleration ramp by Voltage Ramp
I(A)
Start
I Limit
Maximum time
0
P102
Enable
Current Limit
Figure 6.3 – Acceleration Ramp by Current Limit
NOTE!
The time set at P102 is not the exact motor acceleration time,
but the voltage ramp time or the maximum start time. The motor
acceleration time will depend on the motor and the load
characteristics.
100%Un
t(s)
Disable
Rated Current
t(s)
Disable
83