CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Parameter
P103
Voltage Step
during Deceleration
1% Un of the Motor
P104
Deceleration
Ramp Time
P105
End Deceleration
Voltage
P110
Current Limit
1% In of the Motor
84
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Range
[Factory Setting]
Unit
Description / Notes
Used in applications with hydraulic pumps.
99 to 60
Set the rated voltage (%Un), which will be applied to the motor
[ 100=Inactive ]
instantaneously when the Soft-Starter SSW-06 receives the ramp
deceleration command.
For more details about programming and use, refer to Pump Control
at P202.
Used in hydraulic pump applications.
1 to 299
Enables and sets the time of the voltage decrement ramp.
[ 0=Inactive ]
For more details about programming and use, refer to Pump Control.
1s
It can be used as Voltage Ramp control, Pump Control, Current Limit
and Current Ramp.
Used in hydraulic pump applications.
30 to 55
Sets the rated voltage (%Un), which will be applied to the motor at
[ 30 ]
-
the end of the deceleration ramp.
For more details about the programming and use, refer to Pump
Control.
Defines the current limit during the motor start as a percentage of
150 to 500
[ 300% ]
the rated motor current set at P401.
When the current limit is reached during the motor start, the
Soft-Starter SSW-06 will maintain the current at this limit until the
motor reaches the end of the start.
When the current limit is not reached, the motor will start immediately.
For more information about selection of the Current Limit control,
refer to P202.
NOTE!
To enable this function, you must set a deceleration ramp time.
NOTE!
This function is used to lengthen the normal deceleration time of
a load and not to force a shorter time than that imposed by the
load.
U(V)
100%Un
P103
0
Figure 6.4 – Deceleration Ramp by voltage decrement
Stop
P105
t(s)
P104
Disable Voltage Ramp