Parameter
P127
Minimum Stop
Torque
1% Tn of the Motor
P128
Time for Minimum
Stop Torque.
(1)
P130
Pump Control
(1)
P140
External By-pass
Contactor
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Range
[Factory Setting]
Unit
Description / Notes
Here you can program the initial torque limit or an intermediate torque
10 to 100
[ 50 ]
limit for the stop, when a linear torque or a quadratic torque has been
selected at P125.
For more details about programming and application, refer to Torque
Control at P202.
Here you can program the time for the intermediate stop torque, as
1 to 99
[ 50 ]
percent of the maximum time programmed at P104, when the
1% of P104
quadratic torque has been selected at P125.
1 (Constant)
2 (Linear)
3 (Quadratic)
For more details about programming and application, refer to Torque
Control at P202.
This parameter is reserved for future software versions with hydraulic
0
[ 0=Pump ]
pump control type. The current version has been developed for the
-
control of centrifugal hydraulic pump, considering quadratic motor
loads.
For more details about the Pump Control, see P202.
U(V)
P101
0 or 1
[ 0=Inactive ]
-
This function is enabled when the installation of an external By-pass
contactor is required that must be connected parallel to Soft-Starter
SSW-06.
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
P127
1 (Constant)
P127 not used
2 (Linear)
P127 limits the torque when the motor is stopped
3 (Quadratic)
P127 limits the intermediate torque for the stop
Table 6.9 – Function of P127 according to P125
P128
P128 not used
P128 not used (time equal to 0)
P128 time for the intermediate torque limit for the stop process.
Table 6.10 – Function of P128 according to P125
Start
0
P102
Enable
Pump Control
Figure 6.9 – Start and Stop by Pump Control
P140
0 (Inactive)
Without external By-pass contactor
1 (Active)
With external By-pass contactor
Table 6.11 - External By-pass contactor
Action
Action
Stop
100%Un
P103
P104
Disable
Action
P105
t(s)