CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Parameter
P001
Soft- Starter SSW-06
Current
P002
Motor Current
P003
Motor Current
P004
Line Voltage
P005
Line Frequency
P006
Soft-Starter SSW-06
Status
78
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Range
[Factory Setting]
Unit
Description / Notes
 Indicates Soft-Starter SSW-06 output current as percentage of the
0 to 999.9
rated current of the Soft-Starter (%In of the SSW-06) .
[ - ]
 Precision of ± 2% for the full scale. (The full scale is 5x ln of the
0.1%
SSW-06).
 Indicates Soft-Starter SSW-06 Output Current as percentage of the
0 to 999.9
[ - ]
motor rated current (%In of the motor).
0.1%
 Precision of ± 2% for the full scale. (The full scale is 5x ln of the
SSW-06).
 Indicates the Soft-Starter SSW-06 output current in Ampere (A).
0 to 9999.9
 Precision of ± 2% for the full scale. (The full scale is 5x ln of the
[ - ]
0.1A
SSW-06).
 Indicates the average True rms voltage of the tree input phases in
0 to 999
Volts (V).
[ - ]
 Accuracy: ± 2V.
1V
 Indicates the line frequency in Hertz (Hz).
0 to 99
 Precision of ± 5% of the rated frequency of the supply network.
[ - ]
1Hz
 Indicates the actual Soft-Starter SSW-06 status:
XXXX
[ - ]
0 = "rdy"
-
8 = "Sub"
9 = "Exx"
1 = "ruP"
2 = "FuLL" Soft-Starter is enabled at "full voltage";
3 = "PASS" Soft-Starter is enabled with "By-pass";
6 = "ECO"
4 = "rdo"
5 = "br"
6 = "rEv"
7 = "JOG"
11 = "dly" Soft-Starter awaiting the post "delay" stop time;
12 = "G.di" Soft-Starter with "general disable".
NOTE!
When the connection is used inside the delta of the motor
(P150=1), the indication of the current value will already be
multiplied by 1.73.
NOTE!
When the connection is used inside the delta of the motor
(P150=1), the indication of the current value will already be
multiplied by 1.73.
NOTE!
When the connection is used inside the delta of the motor
(P150=1), the indication of the current value will already be
multiplied by 1.73.
NOTE!
Only indicates network frequency when there is a voltage greater
than 20V rms in the power supply (R/ 1L1, S/ 3L2 and T/5L3).
Soft-Starter is ready to be enabled;
Soft-Starter under voltage fault;
Soft-Starter fault;
Soft-Starter is enabled according to "ramp up";
Reserved;
Soft-Starter is enabled according to "ramp down";
Soft-Starter is enabled according to "braking";
Soft-Starter is enabled according to "reversing";
Soft-Starter is enabled according to "jog";