WEG SSW-06.0205 User Manual page 69

Ssw-06 series.
Table of Contents

Advertisement

CHAPTER 5 - START-UP
ACTION
Use the keys
and
select the initial start voltage
Press the key
selected option and exit the
programming mode
Press the key
to go to the next
parameter
Press the key
to enter the
programming mode
Use the keys
and
the ramp time for the start voltage
Press the key
selected option and exit the
programming mode
Press the key
to go to the next
parameter
Press the key
programming mode
Use the keys
and
select the motor rated voltage
70
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
HMI LED DISPLAY
HMI LCD DISPLAY
to
Init. Volt Start
P101=35%
to save the
Init. Volt Start
P101=35%
Start Time Ramp
P102=20s
Start Time Ramp
P102=20s
to select
Start Time Ramp
P102=15s
to save the
Start Time Ramp
P102=15s
Motor Rated Volt
P400=380V
to enter the
Motor Rated Volt
P400=380V
to
Motor Rated Volt
P400=380V
DESCRIPTION
Initial selected voltage:
35% Un
(according to load requirements)
Exit the programming mode
Voltage Ramp Time:
(1 to 999)s
Enter the programming mode.
Selected ramp time for the start
voltage: 15s
(according load requirements)
Exit the programming mode
Motor rated voltage (Un):
(0 to 999)V
Enter the programming mode.
Selected motor rated voltage:
380V
(according to the motor data)