Set the jumpers

If alarm and security jumpers are not installed, the transmitter will operate
normally with the default alarm condition alarm high and the security off.
Procedure
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side. Do not
remove the instrument cover in explosive atmospheres when the
circuit is live.
3. Reposition the jumper. Avoid contact with the leads and the
terminals. See
and OFF positions.
4. Reattach the transmitter cover. The cover must be fully engaged to
comply with explosion-proof requirements.
Figure 4-1: Transmitter Electronics Board
Without LCD display