Set The Switches - Emerson Rosemount 3051 Series Quick Start Manual

Pressure transmitter and flow meter
Hide thumbs Also See for Rosemount 3051 Series:
Table of Contents

Advertisement

Quick Start Guide
4 

Set the switches

Set alarm and security switch configuration before installation as
shown in
The alarm switch sets the analog output alarm to high or low.
Default alarm is high.
The security switch allows (
of the transmitter.
Default security is off (
Use the following procedure to change the swicth configuration:
Procedure
1. If the transmitter is installed, secure the loop, and remove
power.
2. Remove the housing cover opposite the field terminal side.
Do not remove the instrument cover in explosive atmospheres
when the circuit is alive.
3. Slide the security and alarm switches into the preferred
position using a small screwdriver.
4. Reattach the transmitter cover. The cover must be fully
engaged to comply with explosion-proof requirements.
Figure 4-1: Electronics Board
14
Figure
4-1.
Without LCD display
A. Alarm
B. Security
) or prevents (
).
March 2023
) any configuration
With LCD display
Emerson.com/Rosemount

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 3051cf series

Table of Contents