Recommended Wire Sizes (Frame 6)
Description
Main
Power
Field
Recommended Wire Sizes (Frame 7)
Description
Main
Power
Field

Field Grounding Terminals

The field grounding terminals are identified with the International Grounding Symbol
(IEC Publication 417, Symbol 5019).
Operating Ambient Temperature
0°C to 40°C (32°F to 104°F), derate up to a maximum of 50°C. Derate linearly at 1% per degree centigrade for temperature exceeding the maximum
rating ambient for the drive.
External Power Semiconductor Protection Fuses
For details on these input fuses, refer to Appendix E: "Technical Specifications".
DC590+ DRV Series DC Digital Drive
Local wiring regulations always take precedence.
Drive
Input Current
Number of
Size
(A)
Conductors
(A)
1250
1125
4
1650
1485
6
1950
1755
6
60
60
1
Local wiring regulations always take precedence.
Drive
Input Current
Number of
Size
(A)
Conductors
(A)
1200
1100
4
1700
1550
6
2200
2000
6
2700
2450
6
60
60
1
Input
North American
Output Current
Wire Size
(A)
(Kcmil)
500
1250
400
1650
500
1950
AWG 8
60
Input
North American
Output Current
Wire Size
(A)
(Kcmil)
500
1200
400
1700
600
2200
900
2700
AWG 8
60
B-9
Certification
Output
Number of
North American
Conductors
Wire Size
(Kcmil)
4
500
6
500
6
600
1
AWG 8
Output
Number of
North American
Conductors
Wire Size
(Kcmil)
4
500
6
500
6
700
8
700
1
AWG 8