D-32
Programming

CONFIGURE DRIVE

This block contains many of the parameters required for configuring the drive.
NOTE
CONFIGURE ENABLE: The operation of the Block Diagram is suspended and all Keypad LEDs
will flash whilst CONFIGURE ENABLE = TRUE.
NOTE
CONFIGURE DRIVE
Parameter
CONFIGURE ENABLE
Selects Operating Mode (FALSE) or Configuration Mode (TRUE). Refer to "Modifying a Block Diagram", page D-1.
NOM MOTOR VOLTS
Sets the 100% value for Armature Volts VA. Set this value to match the motor in use. (Refer to ARMATURE V CAL in the CALIBRATION
function block).
ARMATURE CURRENT
Sets the 100% value for Armature Current IA. Set this value to match the motor in use.
FIELD CURRENT
Sets the 100% value for Field Current IF. Set this value to match the motor in use. Note: this should be set to a minimum value if in Field Voltage
control - see FLD. CTRL MODE in the FIELD CONTROL function block.
AUTOMATIC SAVE
When TRUE, changes made to parameters using the operator station are automatically saved to the drive's non-volatile memory.
DUMP CHANGED
This parameter is used in conjunction with DUMP MMI (TX) and DUMP BLOCKS. When TRUE, only those parameters that have been modified
from their default value are included in the dump.
UDP USE OP PORT
When TRUE the UDP transfer will be re-directed to the operator station port.
EMULATE 590P
When non-zero the drive emulates some behaviour of earlier firmware versions of the 590P, (firmware versions 5.x and 7.x). This behaviour affects
the time constants of the PID block and the linking of parameters in the function block diagram (refer to "Compatibility with Earlier Versions of
Firmware". page D-7).
DEBOUNCE DIGIN
When TRUE the drive adds a 3ms debounce filter to the digital inputs. This affects terminals C3 to C8, B8 and B9. The hardware connection between
terminal B9, (COAST STOP) and the control of the external contactor is not affected.
The CONFIGURE DRIVE menu on the MMI contains a different set of
parameters, for set-up using the keypad.
The CONFIGURE ENABLE parameter is also available in the following MMI
menus for ease of use: CALIBRATION, CONFIGURE I/O
Tag
39
521
523
524
1220
1169
628
162
1172
Range
FALSE / TRUE
100 to 875 VOLTS
Product code dependent AMPS
Product code dependent AMPS
FALSE/TRUE
FALSE /TRUE
FALSE/TRUE
0x0000 to 0xFFFF
FALSE/TRUE
DC590+ DRV Series DC Digital Drive