Calibrate The Drive - Parker 590+ DRV Product Manual

Table of Contents

Advertisement

4. Connect power but do not start the drive. The drive should now receive control power and the keypad display should read DC 4Q 35A::MENU
LEVEL (the DC 4Q 35A line may vary depending on your drive).
5. Check that the motor is free to rotate.

Calibrate the Drive

Go to the Configure Drive menu to enter the motor calibration data. This is also a good time to enter other commonly used parameter data.
NOTE
To change any parameter in the procedure below, press the M key to access the parameter and then use the arrow keys to change the setting.
When finished, press the E key. At that point you can move to the next parameter.
Press
DC590+ DRV Series DC Digital Drive
Keypad
Display
The DC 4Q 35A line may vary depending on your drive. This is the top of the menu tree.
DC 4Q 35A
MENU LEVEL
You are now viewing the level 1 menu headings.
MENU LEVEL
DIAGNOSTICS
You have navigated to the CONFIGURE DRIVE menu at level 1.
MENU LEVEL
The CONFIGURE ENABLE parameter contained in this menu allows the calibration settings to be
CONFIGURE DRIVE
edited (parameters marked with an asterisk (
changed at any time.
This is the CONFIGURE ENABLE parameter. Press
Press
CONFIGURE DRIVE
CONFIGURE ENABLE
All of the LEDs on the display will flash to indicate the drive is in Configuration mode. The drive will
not run until CONFIGURE ENABLE is set back to DISABLED.
Press
E
to select ENABLED.
to exit.
Calibration and Start-Up
Description
) in this table). Other parameters in this table can be
*
again to edit the parameter.
M
4-3