Ah470330 (Frame 2) - Parker 590+ DRV Product Manual

Table of Contents

Advertisement

3-28
Installing the Drive

AH470330 (Frame 2)

(2 Quad and 4 Quad)
Power supplies for the controller are generated
from the single phase auxiliary supply via a
Switched Mode Power Supply. The incoming
supply is directly rectified to provide a high
voltage dc power rail. A high voltage transistor
switches this rail on to the primary of a high
frequency transformer, the output of which is
rectified and smoothed to provide the dc power
supply rails. The +15V dc rail is monitored via a
reference element and a control signal returned via
an opto-isolator to the control element of the high
voltage switching transistor. The other dc rails
(-15V & +24V dc) are generated via separate
secondary windings which are rectified and
smoothed, with a separate SMPS element
providing a regulated +5V dc rail. The SMPS
operates over an input voltage range of 110V to
240V ac ±10%, 50/60Hz.
Figure 3- 10 590+ Power Board
4 Quad (AH470330)
test points
T4
T1
CONN 30 (heatsink thermistor))
CONN 47 (fan)
CONN 46 (fan)
T7
T10
TB 13
CONN 27
FS6
3 phase and
main contactor
coil
FS5
CONN 17
TB5
CONN 29
(to control board)
T6
T3
T2
Power Board
T9
T12
T11
T8
SMPS
transformer
FS3
field fuses
aux.
fuse
CONN 44
TB6
Terminal Board
DC590+ DRV Series DC Digital Drive
T5
CONN 16
transformer
option