3-51
Installing the Drive

Frame 6: Assembly and Installation

The DC590+ Frame 6 is a high power DC drive and is supplied as a kit of parts ready for mounting onto the back panel of an enclosure. The drive can
be arranged to have the AC input terminals either at the top or the bottom of the drive.
NOTE
The phase assemblies must always be mounted with the fans at the bottom, however, the AC Supply Terminals can be moved to the top of the
drive. Refer to page 3-55.
A kit contains three phase assemblies (each having the same rating), a control panel assembly, and fishplates. Fishplates are used to inter-connect the
DC outputs of the three phase assemblies to produce a 6-pulse stack.
The control panel assembly mounts onto the front of the phase assemblies. The signals to-and-from the control panel assembly provide the operation of
the drive.