Resetting To Factory Defaults (2-Button Reset) - Parker 590+ DRV Product Manual

Table of Contents

Advertisement

6-22
The Keypad
Resetting to Factory Defaults (2-button
reset)
Power-up the drive holding two keys as described below.
The drive is now safely configured with the default settings detailed in this manual for the existing
product code.
The default configuration is not automatically saved to non-volatile memory, so you must perform a
PARAMETER SAVE (refer to "Saving Your Application", page 6-23).
Cloning Feature
The Keypad can be used to transfer all
parameters from a drive to another of the same
rating. You can also use the Keypad to store a
back-up of the drive's parameter settings.
SAVE TO OP will upload all parameter settings
from the drive to the Keypad.
LOAD FROM OP will download all parameter
settings from the Keypad to the drive.
DC590+ DRV Series DC Digital Drive

Hide quick links:

Advertisement

Table of Contents
loading