Recommended Wire Sizes - Parker 590+ DRV Product Manual

Table of Contents

Advertisement

B-8
Certification

Recommended Wire Sizes

North American wire sizes (AWG) are based on NEC/NFPA-70 for ampacities of thermoplastic-insulated (75ºC) copper conductors assuming not
more than three current-carrying conductors in raceway or cable, based on ambient temperature of 40ºC. The wire sizes allow for an ampacity of 125%
of the rated input and output amperes for motor branch-circuit conductors as specified in NEC/NFPA-70.
The table below gives the wire sizes for the input (supply) and output (motor) wiring. The table includes the rated input and output amperes for each
model at 460V or 575V operation.
Recommended Wire Sizes (Frames 1, 2, 3, 4 & 5)
Drive
Size
(A)
Frame 1
15
35
Frame 2
40
70
110
165
Frame 3
180
270
Frame 4 & 5
380
500
725
830
1580
Main power wiring. Local wiring regulations always take precedence.
Input Current
Number of
(A)
Conductors
13.5
1
28.35
1
36
1
63
1
99
1
148.5
1
162
1
243
1
342
1
450
1
653
1
747
1
1427
2
Input
North American
Output Current
Wire Size
(A)
12 AWG
15
8 AWG
35
8 AWG
40
1 AWG
70
1 AWG
110
3/0 AWG
165
4/0 AWG
180
350 Kcmil
270
700 Kcmil
380
1250 Kcmil
500
3 inch bus bar
725
3 inch bus bar
830
4 inch bus bar
1580
Output
Number of
North American
Conductors
Wire Size
1
12 AWG
1
8 AWG
1
8 AWG
1
3 AWG
1
1/0 AWG
1
4/0 AWG
1
4/0 AWG
1
500 Kcmil
1
750 Kcmil
1
1500 Kcmil
1
3 inch bus bar
1
4 inch bus bar
2
4 inch bus bar
DC590+ DRV Series DC Digital Drive