Advanced - Parker 590+ DRV Product Manual

Table of Contents

Advertisement

ADVANCED

These two blocks perform some simple
functions. They are compatible with the special
Link 11 and Link12 used in earlier versions of
this product.
For new configurations, consider using the new
VALUE and LOGIC function blocks.
ADVANCED
Parameter
INPUT 1
General purpose input.
INPUT 2
General purpose input.
ADVANCED
Controls the OUTPUT parameter. When OFF, OUTPUT is the same as INPUT 1. When ON, OUTPUT is the result of the function selected by
MODE.
MODE
This determines which operation is performed on the INPUT 1 and INPUT 2. It can be combined with ADVANCED to dynamically switch the
OUTPUT between INPUT 1 and the result of the selected function. The functionality of the various MODE selections are shown in the table.
OUTPUT
Result of the selected function on the inputs.
DC590+ DRV Series DC Digital Drive
0 : SWITCH
1 : INVERTER
2 : AND
(logic)
3 : OR
(boolean)
4 : SIGN CHANGER
5 : MODULUS
6 : COMPARATOR
Tag
686, 688
687, 689
392, 397
393, 398
712, 713
D-13
Programming
Range
-32768.00 to 32768.00 %
-32768.00 to 32768.00 %
OFF/ON
See below
⎯ .xx V