Calibration and Start-Up

Sequence Status

SEQ STATUS : Tag 537, Mnemonic "ox" (Read Only)
Reserved bits are undefined when read.
Bit Number
0 (lsb)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15 (msb)
Useful Bit Patterns using SEQ STATUS
Tag 537, Mnemonic "ox" (Read Only) - for example:
Sequence Status
0x1B0B
0x044B
0x0447
0x0C47
Mask
Name
Comment
0x0001
Coast Stop
Coast Stop demanded
0x0002
Program Stop
Program (Fast) Stop demanded
0x0004
Disable
/Enable demanded
0x0008
Run
Drive Start demanded
0x0010
Jog
Drive Jog demanded
0x0020
Reserved
Undefined
0x0040
Alarm
Unacknowledged alarm
(Health Store != 0)
0x0080
Reserved
Undefined
0x0100
Running
Contactor in and drive ready to be enabled
0x0200
Enabled
Drive is enabled
0x0400
Zero Speed
Zero speed Output TAG 17
0x0800
Healthy Output
Healthy Output TAG 12
0x1000
Ready
Ready Output TAG 559
0x2000
Reserved
Undefined
0x4000
Reserved
Undefined
0x8000
Reserved
Undefined
Comment
Running
Tripped, Run High
Tripped, Run Low, Enable Low
Trip Acknowledged, Healthy output TRUE Alarm stays high until drive is restarted.
DC590+ DRV Series DC Digital Drive