Parameter Setting Method (Reference) - Mitsubishi Electric FX3U-232-BD User Manual

Melsec-f fx series programmable controllers data communication edition
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
5.2.2

Parameter setting method (reference)

This subsection explains the parameter setting method using the operation panel.
For details on the operation panel, refer to the respective inverter manual.
3-digit monitor LED
Shows the frequency,
parameter number, etc.
Setting dial
Changes the set value of
the frequency and
parameters.
The operating procedure example below shows a case in which the baud rate is set to 19,200 bps.
1
Confirming the RUN indicator and the operation mode
Confirm that the operation is stopped (that the RUN indicator is OFF).
2
Selecting the parameter setting mode
Press the MODE key, and select the parameter setting mode.
Monitor/frequency setting mode
3
Setting the set value of Pr. 30 to "1"
(This step is not necessary if Pr. 30 is already set to "1".)
1. Turn the setting dial to display "P30".
2. Press the SET key to read the currently set value.
3. Turn the setting dial to change the set value to "1".
Press the SET key to set "1".
When the set value and parameter number are displayed alternately, the setting is completed.
Parameter setting mode
The last parameter read
is displayed.
The set value and parameter number are displayed alternately.
5 Communication Setting in Inverter
5.2 S500 Series (When Connected to RS-485 Port)
RUN indicator
Lights or flashes during
operation.
MODE key
Changes over the setting mode.
SET key
Sets each setting.
A
B
C
D
E
F
G
H
I
Apx.A
E-51