Non-Protocol Communication (RS/RS2 Instruction)
10.5

Using RS2 Instruction and Computer Link Communication Together

In FX
, FX
, FX
3S
3G
RS-485) using RS2 instruction can be changed over to computer link by the following methods.
In FX
, FX
, FX
3S
3G
can be checked in the operation mode display devices (D8389, D8419 and D8439).
1. When changing over using RUN mode and STOP mode
Set the communication format as shown below to use non-protocol communication (in accordance with RS-
232C) using RS2 instruction while in RUN mode and then use a protocol for computer link while in STOP mode.
Set computer link using parameters.
Make sure to set the communication format used in the RS2 instruction to D8370, D8400 or D8420, and write
it before executing the RS2 instruction.
X0
MOV
Command
RS2 D1 K1 D2 K1 K1
Non-protocol communication (in accordance with RS-485) cannot be changed over to computer link using
RUN mode and STOP mode.
When changing over non-protocol communication (in accordance with RS-485) to computer link, refer to
"2. When changing over using the RS2 instruction while in RUN mode" below.
2. When changing over using the RS2 instruction while in RUN mode
When changing over non-protocol communication using the RS2 instruction to computer link while in RUN
mode, set the RS2 instruction to OFF, and then overwrite the communication format (D8370, D8400 or
D8420) to "H0000".
Set computer link using parameters.
Before starting up the RS2 instruction again, make sure to properly overwrite the communication format
(D8370, D8400 or D8420) used in the RS2 instruction.
X0
MOV
RS2 D1 K1 D2 K1 K1
X0
MOV
, FX
and FX
PLCs, non-protocol communication (in accordance with RS-232C or
3GC
3U
3UC
, FX
and FX
PLCs, the communication type operating in the communication port
3GC
3U
3UC
P
H0086 D8400
H0086 D8400
P
H0000 D8400
P
10 When Combined with Another Communication