Communication Setting Using Parameter Method (Gx Works2) - Mitsubishi Electric FX3U-232-BD User Manual

Melsec-f fx series programmable controllers data communication edition
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Non-Protocol Communication (RS/RS2 Instruction)
4. Time at which the settings become valid
1) When specifying the settings by parameters
When the PLC power is turned ON, the contents of parameters set on the parameter setting window
using sequence programming software are automatically transferred to D8120, D8129, D8400, D8409,
D8420 and D8429 in the PLC.
As soon as the parameters are transferred to the PLC, the settings become valid.
After the program parameters are transferred to the PLC, it is necessary to turn OFF the PLC power
once, and then turn it ON again.
In FX
, FX
3S
3G
ON from OFF, set the PLC mode to RUN from STOP, and the settings become valid.
2) When specifying the settings by writing data to special data registers
After writing a sequence program, set the PLC mode from STOP to RUN to write the preset data to
D8120, D8400, D8420 or D8370. After that, set the PLC mode to STOP once, and then set it to RUN
again. Or turn OFF the PLC power once, and then turn it ON again.
As soon as the PLC mode is set to RUN from STOP or the PLC power is turned ON from OFF, the
settings become valid.
In FX
, FX
3S
3G
to RUN from STOP, and the settings become valid.
If change of the setting becomes necessary while the RS or RS2 instruction is being driven, set the RS or
RS2 instruction to OFF, set D8120, D8400, D8420 and D8370 to "0", and then set a new value to them.
5.2

Communication Setting Using Parameter Method (GX Works2)

Communication settings may be changed via the parameter method with GX Works2, GX Developer,
FXGP/WIN for Windows and FX-30P handy programming panel. It is not possible to set ch0 in FX
FX
PLCs using parameters. This section describes how to change parameters with GX Works2.
3GC
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.
5.2.1
Operating procedure
This subsection explains the serial communication setting method. Suppose that GX Works2 is already
started up.
1
Opening the parameter setting window
In the project view area of the navigation window, double-click [Parameter]  [PLC Parameter].
If the navigation window is not displayed, select [View]  [Docking Window]  [Navigation] from
the menu bar.
, FX
PLC, after the programs (parameters) are transferred to the PLC, turn the power
3GC
, FX
PLC, after writing the preset data, turn the power ON from OFF, set the PLC mode
3GC
For details on FXGP/WIN operating procedure, refer to section 5.3.
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.
5 Communication Setting in FX Programmable Controller
5.2 Communication Setting Using Parameter Method (GX Works2)
A
B
C
D
E
and
3G
F
G
H
I
Apx.A
F-41