When Using 232Bd Or 232Adp - Mitsubishi Electric FX3U-232-BD User Manual

Melsec-f fx series programmable controllers data communication edition
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Programming Communication
3. Connection of the FX-2PIF
The FX-2PIF cannot be connected to the 422BD.
Connect it to the standard port.
2.3.2

When using 232BD or 232ADP

When the 232BD or 232ADP is attached to a PLC, it consumes the current shown in the table below. Make
sure that the power capacity of 5V DC in the FX
Model name
FX
-232-BD
3U
FX
-232-BD
2N
FX
-232ADP(-MB)
3U
FX
-232ADP
2NC
FX
-232ADP
0N
2.3.3
Other cautions
1. For FX
, FX
1S
1) Verify that the communication format is in the initial status (D8120 = K0).
Check the communication parameters using the peripheral equipment.
If the communication is set so that non-protocol procedure (RS instruction) or a dedicated protocol is
used, clear the setting to "0" using the peripheral equipment.
2) If RS instruction is used in the program, delete it, turn OFF the PLC power, and then turn it ON again.
2. For FX
(Ver. 2.00 or later) and FX
2N
1) Verify that the communication format is in the initial status (D8120 = K0).
Check the communication parameters using the peripheral equipment.
If the communication is set so that non-protocol procedure (RS instruction) or a dedicated protocol is
used, clear the setting to "0" using the peripheral equipment.
2) If RS instruction is used in the program, do not execute it. If it is executed, the PLC operates according to
RS instruction.
3. For FX
(Ver. 3.00 or later) and FX
2N
1) Verify that the communication format is in the initial status (D8120 = K0).
Check the communication parameters using the peripheral equipment.
If the communication is set so that non-protocol procedure (RS instruction) or a dedicated protocol is
used, clear the setting to "0" using the peripheral equipment.
2) If RS instruction is used in the program, do not execute it. If it is executed, the PLC operates according to
RS instruction.
3) If EXTR instruction is used in the program, delete it, turn OFF the PLC power, and then turn it ON again.
4. For FX
, FX
3S
1) Verify that the communication format for the communication port used in programming communication is
set correctly (D8370, D8120, D8400, D8420 = K0).
Check whether the communication parameters are set correctly using the peripheral equipment.
2) Verify that the RS or RS2 instructions are not executed in the program for the communication port used in
programming communication.
Do not execute RS and RS2 instructions.
3) If an inverter communication instruction is used in the program for the communication port used in
programming communication, delete it, turn OFF the PLC power, and then turn it ON again.
5. Connection of (5V power type) GOT unit
When using the (5V power type) GOT unit together with the FX
either the standard built-in port (RS-422) or the FX
the FX
, FX
3S
3G
H-24
Power consumption
at 5 VDC
20 mA
20 mA
30 mA
100 mA
200 mA
, FX
and FX
(whose version is before Ver. 2.00) PLCs
1N
1NC
2N
, FX
, FX
and FX
3G
3GC
3U
PLC at the same time.
, FX
, FX
, FX
1NC
2N
2NC
FX
FX
1NC
2N
(versions earlier than Ver. 3.00) PLCs
2NC
(Ver. 3.00 or later) PLCs
2NC
PLCs
3UC
, FX
3S
-422-BD. It is not allowed to connect two GOT units to
3G
2 System Configuration and Selection
2.3 Caution on Selection
and FX
PLCs is not exceeded.
3U
3UC
: Applicable
—: Not attachable
FX
3UC
FX
FX
(D, DS,
2NC
3U
DSS)
PLC, connect only one GOT unit to
3G
FX
3UC
(LT,
LT(-2))